Technical Data | |
Inputs | |
Number: | 4 voltage and current (3 phases + neutral) |
Maximum voltage: | 1000 Vrms (6 kV peak) |
Maximum sampling speed: | 200 kS/s on each channel simultaneously |
Volt/Amps/Hertz | |
Vrms (AC + DC) Measurement range: | 1 … 1000 V |
Accuracy: | 0.1% of Vnom |
Vpeak Measurement range: | 1 … 1400 V |
Accuracy: | 5% of Vnom |
Crest factor, voltage Measurement range: | 1.0 … > 2.8 |
Accuracy: | ±5% |
Arms (AC + DC) Measurement range: | 0 … 20 kA |
Accuracy: | ±0.5% ± 5 counts |
Apeak Measurement range: | 0 … 5.5 kA |
Accuracy: | 5% |
Crest factor, A Measurement range: | 1 … 10 |
Accuracy: | ±5% |
Hz 50 Hz nominal Measurement range: | 40 … 70 Hz |
Accuracy: | ±0.01 Hz |
Dips and swells | |
Vrms (AC+DC) 2Measurement range: | 0.0% … 100% of Vnom |
Accuracy: | ±0.2% of nominal voltage |
Arms (AC+DC) ? Measurement range: | 0 …. 20 kA |
Accuracy: | ±1% … ± counts |
Harmonics | |
Harmonic (interharmonic) (n) Measurement range: | DC, 1..50; (Off, 1..49) measured according to IEC 61000-4-7 |
Vrms Measurement range: | 0.0 … 1000 V |
Accuracy: | ±0.05% of nominal voltage |
Arms Measurement range: | 0.0 ± 4000 mV x clamp scaling |
Accuracy: | ±5% ± 5 counts |
Watts Measurement range: | Depends on clamp scaling and voltage |
Accuracy: | ±5% ± n x 2% or reading, ± 10 counts |
DC voltage Measurement range: | 0.0 ± 1000 V |
Accuracy: | ±0.2% of nominal voltage |
THD Measurement range: | 0.0 … 100.0% |
Accuracy: | ±2.5% V and A (± 5% Watt) |
Hz Measurement range: | 0 … 3500 Hz |
Accuracy: | ± 1 Hz |
Phase angle Measurement range: | -360° … +360° |
Accuracy: | ± n x 1.5° |